FD2D-A

1-1/2 Hour Rated - Dynamic Fire Damper

Overview

The FD2D-A fire damper employs curtain style blades for point-of-origin control of fire in static and dynamic HVAC systems. The FD2D-A is qualified to 4,000 ft/min (20.3 m/s) and 4 in.wg. (1.0 kPa) and may be installed in vertical walls or partitions with fire resistance ratings up to 2 hours.
 

Resources

Product Sheets

Installation Instructions

Accessories

Standard Construction

Frame: 22 ga. (0.85) galvanized steel.
Blades: 24 ga. (0.7) galvanized steel - curtain style.
Fire Closure Device: Fusible link.
Fire Closure Temperature: 165oF (75oC)
Minimum Size: 6" x 6" (152 x 152)
Maximum Size: Single Section: Vertical: 36" x 48" (914 x 1219)
                           Multiple Section: Vertical: 72" x 36" (1829 x 914)
                                                                    36" x 72" (3048 x 1829)