3 Hour - Ceiling Radiation Damper
The RD-4 ceiling radiation damper employs low profile butterfly style blades for point-of-origin control of radiant heat in HVAC systems. The RD-4 is installed horizontally in the ceiling membrane of floor-ceiling or roof-ceiling assemblies with fire resistance ratings up to and including 3 hours. The RD-4 is specifically designed for assemblies having limited space between the ceiling membrane and the structure above.
Frame: 22 ga. (0.85) galvanized steel.
Blades: 22 ga. (0.85) galvanized steel - butterfly. Insulated with ceramic refractory material for dampers larger than 114 in2 (735 cm2).
Fire Closure Device: Fusible Link.
Fire Closure Temperature: 165oF (75oC).
Minimum Size: 6" x 12" (152 x 305)
Maximum Size: 24" x 24" (610 x 610)
NEED HELP?
Need help finding the right solution for your project? Connect with your local C&S representative for expert product selection, specifications, technical guidance, and installation support.
Find Your Local Representative