FSD-181-OP

Model FSD-181-OP

1-1/2 Hour - Combination Fire Smoke Damper
Airfoil Blade - Out-of-Partition

The FSD-181-OP combination fire smoke damper employs triple-V blades for point-of-origin control of fire and smoke in static and dynamic smoke management systems. These specialty dampers are approved for installation with the closed plane of the blades up to 14-1/2" (368) outside the fire rated partition and come standard with the actuator in the airstream allowing for direct service access fromThe FSD-181-OP is qualified to 4,000 ft/min (20.3 m/s) and 8 in.wg. (2.0 kPa) and may be installed in vertical walls or partitions, or horizontally in floors or assemblies with fire resistance ratings up to 2 hours.


Standard Construction

Frame: 5" x 1" (127 x 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 ga. (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high.
Blades: 6" x 14 ga. (152 x 2.0) galvanized steel - airfoil.
Sleeve: 16" x 20 ga. (406 x 1.0) galvanized steel.
Axles: 1/2" (13) diameter plated steel hex.
Linkage: Concealed in frame.
Bearings: Stainless steel oilite, sleeve-type.
Seals: Silicone blade edge seals inegrally rolled and mechanically fastened to blades. Flexible metal jamb seals.
Actuator: 120 VAC, power-open, spring-close, internal mount. View Actuators.
Fire Closure Device: HS-10 (electric actuators)
                                    PFV (pneumatic actuators)    
Fire Closure Temperature: 165oF (75oC)
Minimum Size: 10" x 6" (250 x 152)
Maximum Size: 36" x 36" (914 x 914)


Ratings

UL 555 Fire Resistance Rating: 1-1/2 hour (vertical and horizontal)
UL 555S Leakage Class: 1 
Maximum Temperature: 350oF (177oC)

UL 555 and 555S Listing: R14981
CSFM Listing: 3225-1404:107 and 3230-1404:108
New York City MEA Listing: 295-98-E
Meets NFPA Standards: 90A, 92A, 92B and 101
Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC