FSD-122-OP

1-1/2 Hour - Combination Fire Smoke Samper

Common Applications

  • Wood Truss Assemblies
  • Multifamily
  • Light Commercial

Resources

Product Sheets

Installation Instructions

Accessories

Overview

The FSD-122-OP combination fire smoke damper employs triple-V blades for point-of-origin control of fire and smoke in static and dynamic smoke management systems. These specialty dampers are approved for installation with the closed plane of the blades up to 14-1/2" (368) outside the fire rated partition and come standard with the actuator in the airstream allowing for direct service access from the face of the damper through HVAC grille. The FSD-122-OP is qualified to 2,000 ft/min (10.2 m/s) and 4 in.wg. (1.0 kPa) and may be installed in vertical walls or partitions, or horizontally in floors or assemblies with fire resistance ratings up to 2 hours.

Standard Construction

Frame: 5" x 1" (127 x 25) galvanized steel hat channel with inerlocking corner gusset. Equivalent to 13 ga. (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high.
Blades: 6" x 16 ga. (152 x 1.6) galvanized steel - triple-V.
Sleeve: 20 ga. (1.0) galvanized steel with 1" (25) flange and factory instaled thermal insulation on four sides.
Axles: 1/2" (13) diameter plated steel hex.
Linkage: Concealed in frame.
Bearings: Stainless steel oilite, sleeve-type.
Seals: Silicone blade edge seals and flexible metal jamb seals.
Actuator: 120 VAC, power-open, spring-close, internal mount. 
Fire Closure Device: HS-10 (electric actuators)
                                    PFV (pneumatic actuators)    
Fire Closure Temperature: 165oF (75oC)
Minimum Size: 10" x 6" (254 x 152)
Maximum Size: 36" x 48" (914 x 1219)