Document Cart
Model FD4D-IMA
1-1/2 Hour - Dynamic Rated - Fire Damper
Integral Mounting Angle - Curtain Style Blade
The FD4D-IMA fire damper employs curtain style blades and a factory installed integral mounting angle for point-of-origin control of fire in static and dynamic HVAC systems. The integral mounting angle is designed and approved to be fastened directly to the fire separation and may be installed under the drywall in metal stud construction. The FD4D-IMA is qualified to 4,000 ft/min (20.3 m/s) and 4 in.wg. (1.0 kPa) and may be installed in vertical walls or partitions with fire resistance ratings up to 2 hours.
Standard Construction
Sleeve/Frame: Integral 12" x 20 ga. (305 x 1.0) galvanized steel with 1-1/2" x 20 ga. (38 x 1.0) galvanized steel inegral single side mounting angle.
Blades: 24 ga. (0.7) galvanized steel - curtain style.
Fire Closure Device: UL Listed Fusible link.
Fire Closure Temperature: 165oF (75oC)
Minimum Size: 6" x 6" (152 x 152)
Maximum Size: Single Section: Vertical: 36" x 48" (914 x 1219)
Ratings
UL 555 Fire Resistance Rating: 1-1/2 hour (vertical)
UL 555 Listing: R14981
CSFM Listing: 3225-1404:101
New York City MEA Listing: 295-98-E
Meets NFPA Standards: 90A, 92A, 92B and 101
Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC